<?xml version="1.0" encoding="UTF-8"?>
<!DOCTYPE article PUBLIC "-//NLM//DTD JATS (Z39.96) Article Authoring DTD v1.4 20240229//EN" "JATS-articleauthoring1.dtd">
<article article-type="research-article" xml:lang="zh-CN" xmlns:xlink="http://www.w3.org/1999/xlink">
  <front>
    <journal-meta>
      <journal-id journal-id-type="publisher-id">58</journal-id>
      <journal-title-group>
        <journal-title>施工技术研究</journal-title>
        <abbrev-journal-title>Research on Construction Technology</abbrev-journal-title>
      </journal-title-group>
      <issn>ISSN: 3104-8129 EISSN: 3104-8137</issn>
      <publisher>
        <publisher-name>睿核出版社有限公司</publisher-name>
      </publisher>
    </journal-meta>
    <article-meta>
      <article-id pub-id-type="doi">10.65700/RHSGJSYJ01-2611-8129-0555</article-id>
      <article-id pub-id-type="publisher-id">17337</article-id>
      <title-group>
        <article-title>高低压开关柜发热缺陷检测与快速处置技术探析</article-title>
      </title-group>
      <contrib-group>
        <contrib contrib-type="author">
          <string-name>陈文</string-name>
        </contrib>
        <contrib contrib-type="author">
          <string-name>张洪吉</string-name>
        </contrib>
      </contrib-group>
      <pub-date pub-type="epub">
        <year>2026</year>
        <month>3</month>
      </pub-date>
      <issue>3</issue>
      <abstract>
        <p>高低压开关柜作为配电系统中的核心设备，其运行状态直接关系到供电安全、设备寿命及现场生产连续性。实际运维中，因触
头接触电阻增大、母排连接松动、绝缘老化、柜内散热不良及负荷波动等因素引起的发热缺陷较为常见，若未能及时识别和快速处置，极
易演变为停电事故、设备烧损甚至人身风险。本文立足一线运维检修实践，围绕高低压开关柜发热缺陷的成因、检测方法、诊断流程与快
速处置技术展开系统分析。文章首先阐述发热缺陷的典型表现与影响机理，其次对红外测温、在线测温、局部放电辅助判断、负荷电流比
对及停电解体检查等手段的适用范围进行总结，进一步提出分级研判、现场隔离、带电监测、停电检修和闭环验收的快速处置模式。同时
结合典型工况构建检测指标与处置策略数据表，为基层班组开展隐患治理提供参考。研究表明，建立“巡检发现—数据校核—风险分级—
快速处置—复测验证”的工作链条，可显著提高发热缺陷发现率和处置时效，降低重复缺陷发生概率。本文成果对提升配电设备精益运维
水平、保障电网安全稳定运行具有较强实用价值。</p>